Type MC Cable - Isolated Ground is constructed with soft-drawn copper, Type THHN/THWN conductors rated 90°C dry available in sizes 12 AWG and 10 AWG, and two insulated grounding conductors--one solid green and the second green with yellow stripes. The conductors are cabled together and a binder tape bearing the print legend iswrapped around the assembly. Aluminum interlocking armor is applied over the assembly.
Type MC Cable - Isolated Ground is constructed with soft-drawn copper, Type THHN/THWN
conductors rated 90°C dry available in sizes 12 AWG and 10 AWG, and two insulated grounding conductors--one solid green and the second green with yellow stripes. The conductors are cabled together and a binder tape bearing the print legend iswrapped around the assembly. Aluminum interlocking armor is applied over the assembly.
Type AC Cable BX is constructed with soft-drawn copper, Type THHN insulated conductors which are
individually wrapped with a moisture-resistant, flame-retardant paper covering. Aluminum interlocking armor is applied over the assembly. A 16 AWG aluminum bond wire is placed inside the armor, runs longitudinally and is in intimate contact with the armor for its entire length.
Power Tray Cable Applications
Type MC Cable is suitable for use as follows:
• Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
Type AC Cable is suitable for use as follows:
• Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
STANDARDS & REFERENCES
Type AC Cable meet or exceeds the following requirements
• UL 4, 83, 1581, 2556
• Federal Specification A-A59544 (formerly J-C-30B)
• National Electrical Code Article 320 Armored Cable: Type AC
Type MC Cable meets or exceeds the requirements of the following
• UL 83
• UL 1569
• UL 1685
• Federal Specification A-A59544 (formerly J-C-30B)
• FT4/IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
• NEC
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
CONSTRUCTION
Type MC Cable is constructed with soft-drawn copper, Type THHN/THWN conductors rated 90°C dry
available in sizes 14 AWG through 2 AWG, and a green insulated grounding conductor. The conductors are cabled together and a binder tape bearing the print legend is wrapped around the assembly. Aluminum interlocking armor is applied over the assembly.
Type AC Cable is constructed with soft-drawn copper, Type THHN insulated conductors which are
individually wrapped with a moisture-resistant, flame-retardant paper covering. Aluminum interlocking armor is applied over the assembly. A 16 AWG aluminum bond wire is placed inside the armor, runs longitudinally and is in intimate contact with the armor for its entire length.
.
| Conductor Size | Solid or Stranded | Grounding Conductor Size | Overall Diameter | Weight | Ampacity (Amps) | ||
| (AWG) | (AWG) | (inches) | (lbs./1000ft.) | 60 | 75 | 90 | |
| 14-2 | Solid | 14 | 0.439 | 77 | 15 | 15 | 15 |
| 14-3 | Solid | 14 | 0.464 | 94 | 15 | 15 | 15 |
| 14-4 | Solid | 14 | 0.494 | 112 | 15 | 15 | 15 |
| 12-2 | Solid | 12 | 0.527 | 137 | 20 | 20 | 20 |
| 12-3 | Solid | 12 | 0.505 | 129 | 20 | 20 | 20 |
| 12-4 | Solid | 12 | 0.539 | 155 | 20 | 20 | 20 |
| 10-2 | Solid | 10 | 0.542 | 150 | 30 | 30 | 30 |
| 10-3 | Solid | 10 | 0.58 | 189 | 30 | 30 | 30 |
| 10-4 | Solid | 10 | 0.623 | 229 | 30 | 30 | 30 |