SEU Cable

May be used as service-entrance conductors, feeders and branch circuits where SE cables are permitted when installed as specified by the National Electrical Code® (NEC). May be used in wet or dry locations at temperatures up to 90°C.Uninsulated conductor between two insulated conductors, parallel-laid then wrapped in a glass-reinforced tape. Uninsulated (bare) conductor may be used for equipment grounding where used for feeder or branch circuit applications. Gray, sunlight-resistant PVC jacket o

Service Entrance Cable

Type SE, Style U

 600V

 90°C Wet or Dry

Description: 

May be used as service-entrance conductors, feeders and branch circuits where SE cables are permitted when installed as specified by the National Electrical Code® (NEC). May be used in wet or dry locations at temperatures up to 90°C.

 Uninsulated conductor between two insulated conductors, parallel-laid then wrapped in a glass-reinforced tape. Uninsulated (bare) conductor may be used for equipment grounding where used for feeder or branch circuit applications. Gray, sunlight-resistant PVC jacket over the complete assembly.

 Materials: 

Stranded conductors: Uncoated copper per ASTM B3, ASTM B8, and ASTM B787. Insulated conductors: Type THHN/THWN-2 insulation. Black PVC insulation with black nylon. Rated for use up to 90°C in wet or dry locations. Phase ID: A red stripe on insulation surface of one conductor. Uninsulated conductor: Bare stranded copper.

core and outer sheath meet the 720-hour sunlight resistance requirement.

Technical Data
 Conductor Size
(AWG, Kcmil)
Phase ConductorNeutral ConductorNominal ThicknessSheath ThicknessDia.Weight(kg/km)
Dia.Dia.mm
2×8AWG+1×8AWG3.343.341.140.76 12.3 158 
2×6AWG+1×6AWG4.224.221.140.76 14.2 214 
2×4AWG+1×4AWG5.325.31.140.76 16.6 299 
2×4AWG+1×6AWG5.324.221.140.76 15.8 274 
2×2AWG+1×4AWG6.705.321.140.76 18.6 387 
2×2AWG+1×2AWG6.706.701.140.76 19.6 426 
2×1AWG+1×3AWG7.535.981.400.79 21.1 489 
2×1AWG+1×1AWG7.537.531.400.81 22.2 540 
2×1/0AWG+1×2AWG8.466.701.400.83 23.0 590 
2×1/0AWG+1×1/0AWG8.468.461.400.85 24.3 654 
2×2/0AWG+1×1AWG9.507.531.400.87 25.2 715 
2×2/0AWG+1×2/0AWG9.509.501.400.90 26.6 795 
2×3/0AWG+1×1/0AWG10.668.461.400.92 27.6 871 
2×3/0AWG+1×3/0AWG10.6610.661.400.95 29.3 971 
2×4/0AWG+1×2/0AWG11.989.501.400.97 30.4 1065 
2×4/0AWG+1×4/0AWG11.9811.981.401.00 32.2 1189 
2×250MCM+1×3/0AWG13.0210.661.651.03 33.5 1288 
2×250MCM+1×250MCM13.0213.021.651.06 35.3 1419 















3×8AWG+1×8AWG3.343.341.140.76 14.0 207 
3×6AWG+1×6AWG4.224.221.140.76 16.2 282 
3×4AWG+1×6AWG5.324.221.140.76 18.2 369 
3×4AWG+1×4AWG5.325.321.140.76 18.8 394 
3×2AWG+1×4AWG6.705.321.140.80 21.4 528 
3×2AWG+1×2AWG6.706.701.140.81 22.3 568 
3×1AWG+1×3AWG7.535.981.400.85 24.4 672 
3×1AWG+1×1AWG7.537.531.400.87 25.4 722 
3×1/0AWG+1×2AWG8.466.701.400.90 26.6 811 
3×1/0AWG+1×1/0AWG8.468.461.400.92 27.7 874 
3×2/0AWG+1×1AWG9.507.531.400.94 29.1 983 
3×2/0AWG+1×2/0AWG9.509.501.400.97 30.3 1062 
3×3/0AWG+1×1/0AWG10.668.461.401.00 31.8 1198 
3×3/0AWG+1×3/0AWG10.6610.661.401.02 33.2 1296 
3×4/0AWG+1×2/0AWG11.989.501.401.06 35.0 1464 
3×4/0AWG+1×4/0AWG11.9811.981.401.09 36.6 1587 
3×250MCM+1×3/0AWG13.0210.661.651.13 38.6 1767 
3×250MCM+1×250MCM13.0213.021.651.16 40.1 1897 















4×8AWG+1×8AWG3.343.341.140.76 15.8 256 
4×6AWG+1×6AWG4.224.221.140.76 18.1 349 
4×4AWG+1×6AWG5.324.221.140.78 20.6 467 
4×4AWG+1×4AWG5.325.321.140.79 21.2 493 
4×2AWG+1×4AWG6.705.321.140.85 24.3 672 
4×2AWG+1×2AWG6.706.701.140.87 25.1 712 
4×1AWG+1×3AWG7.535.981.400.92 27.7 858 
4×1AWG+1×1AWG7.537.531.400.93 28.6 908 
4×1/0AWG+1×2AWG8.466.701.400.96 30.2 1035 
4×1/0AWG+1×1/0AWG8.468.461.400.98 31.1 1098 
4×2/0AWG+1×1AWG9.507.531.401.02 33.0 1254 
4×2/0AWG+1×2/0AWG9.509.501.401.04 34.1 1332 
4×3/0AWG+1×1/0AWG10.668.461.401.08 36.1 1528 
4×3/0AWG+1×3/0AWG10.6610.661.401.10 37.3 1626 
4×4/0AWG+1×2/0AWG11.989.501.401.15 39.6 1868 
4×4/0AWG+1×4/0AWG11.9811.981.401.17 41.0 1990 
4×250MCM+1×3/0AWG13.0210.661.651.23 43.8 2253 
4×250MCM+1×250MCM13.0213.021.651.25 45.1 2382 

 Standards:

UL 83: E15119

UL 854: E11098

ASTM B3

ASTM B8

ASTM B787

Federal Specification A-A-59544

NFPA 70 (National Electrical Code®)

Surface Print:

Sample: TYPE SE STYLE U TYPE THHN

OR THWN-2 2 CDRS 6 AWG 1 CDR 8

AWG 600V E11098-A (UL)


SEU Cable
May be used as service-entrance conductors, feeders and branch circuits where SE cables are permitted when installed as specified by the National Electrical Code® (NEC). May be used in wet or dry locations at temperatures up to 90°C.Uninsulated conductor between two insulated conductors, parallel-laid then wrapped in a glass-reinforced tape. Uninsulated (bare) conductor may be used for equipment grounding where used for feeder or branch circuit applications. Gray, sunlight-resistant PVC jacket o
Long press to look detail
Long by picture save/share
INQUIRY

ONLINE INQUIRY MORE+
  • Name *

  • E-mail *

  • Phone

  • Describe

  • Submit

  • Security Code
    Refresh the code
    Cancel
    Confirm

Inquiry Content:


You have no items to require

Add Successfully
INQUIRY

ONLINE INQUIRY MORE+
  • Name *

  • E-mail *

  • Phone

  • Describe

  • Submit

  • Security Code
    Refresh the code
    Cancel
    Confirm

Inquiry Content:


You have no items to require

Add Successfully

Contact Supplier

Send your message to this supplier

  • Name *

  • Email *

Subscribe

Security Code
Refresh the code
Cancel
Confirm

About Us

Products

About Us

Products

News

Copyright © Hualue Co., Ltd   All Rights Reserved. 

添加微信好友,详细了解产品
使用企业微信
“扫一扫”加入群聊
复制成功
添加微信好友,详细了解产品
我知道了